C Machine Usage
水管(guan)安裝示意圖(tú) Installation schemes

用途:用(yong)于給水槽的(de)水進行降溫(wēn)。
特點:根(gen)據水槽水質(zhi)含防粘劑化(huà)工産品腐蝕(shi)性高的弊病(bing),采用純钛管(guan)蒸發器,熱傳(chuán)遞好耐腐蝕(shi),改進了傳統(tǒng)的銅管蒸發(fā)器缺點。
公共(gong)設備電力:電(diàn)壓380V,50Hz。
①管道泵:2.2kw 兩(liang)台
②冷卻塔:15噸(dun)
③塑料管1.5寸到(dao)噴水管爲4分(fen)管
④主電源線(xiàn):10平方 四芯線(xiàn)
⑤水泵電源線(xian):2.5平方 三芯線(xian)
Technical Parameters | |
型号 Model | LJ-15HP |
機型Systems | 15HP |
外型尺寸 Appearance Size: L*W*H(mm) | 4850*1450 |
功率(lǜ)Power (KW) | 11 |
重(zhong)量Weight(kg) |
●上班:開機(ji)順序:提前十(shí)分鍾開機
1. 閉(bì)合冰水循環(huan)泵
2. 閉合熱水(shui)循環泵
3. 再閉(bì)壓縮機循環(huán)泵
●下班(ban):随時斷電順(shùn)序:
3. 斷開冰(bīng)水泵
●移交時(shi):1. 高低壓的正(zheng)常值是幾公(gong)斤,高低壓控(kong)制器的設定(dìng)值是幾公斤(jin),進行電流是(shi)幾安,設定保(bao)護值是幾安(ān),均要記錄。
2. 機(ji)台維修前請(qing)參考以上的(de)正常值,維修(xiu)前要清洗幹(gàn)淨外觀和油(you)漬的位置,便(bian)于電工機修(xiu)工維修人員(yuan)的操作。
3. 空氣(qì)開關不可以(yi)随意換大的(de),以免燒毀壓(yā)縮機。
維修保(bao)養 Maintenance
常見(jian)小問題 Common small problem
●冰水(shuǐ)循環:進料的(de)噴水管出水(shui)量小
1.水槽吸水口(kou)粗過濾網賭(du)了碎膠料。
2.管道(dào)過濾器的不(bú)鏽鋼濾網堵(dǔ)塞
清洗(xǐ)方法:務必停(tíng)機水泵,取出(chu)濾網清洗幹(gan)淨。裝好方可(kě)開機。
●熱水循(xún)環:手摸冷卻(que)塔的水溫感(gan)覺比常溫高(gāo)。原因:冷卻塔(ta)高溫狀态易(yì)産生污垢,循(xun)環水量不夠(gòu),散熱管道不(bú)通暢。
清洗方(fang)法: 1. 先将冷卻(que)塔底盤污垢(gou)打掃幹淨。
3. 打開冷凝(ning)端蓋,用焊在(zài)鋼筋上鐵刷(shua)子刷通管道(dào)。
:需換清水(shui)三次,方可正(zhèng)常使用避免(mian)除垢劑腐蝕(shí)水泵元件及(ji)制冷管道。
2. 水泵壞(huai)。冷卻塔風機(jī)不轉。
3. 冷凝管(guǎn)道污垢機過(guò)多。
6. 制(zhì)冷劑注入量(liàng)過多或更換(huàn)部件時沒有(you)經嚴格真空(kong),系統含有空(kōng)氣。
●低壓跳:1. 冰(bīng)水通道堵塞(sāi)(參考冰水循(xun)環排除)引起(qǐ)蒸發钛炮結(jié)霜。
2. 制冷劑漏(lou)到靜止不足(zu)五公斤時。
3. 冷(leng)媒通道微堵(dǔ)不順口,如過(guò)濾器進出有(yǒu)溫差,手閥進(jin)出有溫差。
少見(jian)故障 Rare fault
壓縮機(jī)不工作:1. 冰水(shuǐ)泵正常運轉(zhuan)否。
2. 熱水器正(zhèng)常運轉否。
4. 檢(jiǎn)查空氣開關(guan),接觸器,繼電(dian)器,壓力開關(guān),溫控器等電(dian)路由專業電(diàn)工檢修。
冷炮(pào) evaporator 熱炮 condenser風機 fan 開(kāi)水閥 water valve手閥 handvalve 水(shuǐ)泵 water pump
細濾 fine filter 粗濾(lü) coarse filter開關 switch 噴水管(guǎn) spray pipe球閥開關 ball valve switch此(cǐ)不可裝開關(guan) Don’t fix switch here.
Purpose: Used to cool the water in the sink
Advantage: According to the water quality of the flume contains anti - adhesive chemical products corrosion high disease,Pure titanium tube evaporator,Good heat transfer corrosion resistance,The shortcomings of traditional copper tube evaporator are improved.
Public equipment:Power: 380V,50Hz.
②Cooling tower: 15tons
③Plastic pipe(1.5inches)to water pipe(0.4 inches)
⑤ Water pump:2.5 mm² three-core
型号 Model | LJ-15HP |
機型Systems | 15HP |
外型尺寸(cun) Appearance Size: L*W*H(mm) | 100*50*1450 |
功(gong)率Power (KW) | 11 |
400 |
2. Close the hot water circulation pump
3. Close compressor circulation pump
●After work: the steps of end power at any time:
1. Sconnect compressor
2. Disconnect hot water circulation pump
3. Disconnect the ice water pump
●Hand over:1.We should record the data as follow: the normal value of high-low pressure (kilograms),The setting value of high-low pressure controller (kilograms),The running current (amperes),The setting value of protection (amperes)
2. Please refer to the above normal values before the machine maintenance, clean cover and the position of oil in order to be convenient for repairman to operate.
3. Air switch can’t be change to a bigger one, in case of burning compressor.
Maintenance
Clean cooling tower at every three monthes, change the sink’s water at every ten days to fifteen days, (so as not to affect the material) infuse the oil into bearing at every three monthes, avoid dry damage, shift.
FAQ
●Ice water circulation: The water yield of the feed-in spray pipe is small.
Reasons: 1.The fragmentary rubber compoud is pluged up because
2. The stainless steel strainer of piping filter is pluged.
The cleaning method: Be sure to stop the pump, take out mesh to clean. Boot only after pack.
●Hot water circulation: The feeling temperature by touching cooling tower is higher than normal temperature.
Reason: The cooling tower is easy to produce dirt at high temperature, circulation water is not enough, heat pipe is obstructed.
1. First clean the cooling tower chassis’s dirt.
2. Add water and appropriate cleaner, open cycle pump running softening for 6-8 hours.
3. Open the cover of condensation, brush the pipeline by iron brush on steel bar.
4. Remember: change clear water three times to avid that cleaner corrode pump components and refrigeration pipeline corrosion.
●High pressure jump:
1. The cooling tower has too much dirt, the water spray of the cooling tower is jamed and not work.
2. Water pump doesn’t work. The fan of cooling tower doesn’t work.
4.Impeller congestion, not to be automatic to fill water etc, these reasons cause the water flow is not enough, and water pressure is too small to lead to jump.
6. The injection quantity of refrigerants is too much or when replace parts without the strict vacuum, containing the air in the system.
●Low pressure jump
1. The cool water channel is jamed (reference ice water circulation to exclude) which cause evaporation titanium gun frost.
2. Refrigerants lead to the static is not to have five kilograms.
4. Ice water pump configuration doesn’t reach enough power.
Rare glitches
1. Whether the ice water pump works normally.
2. Whether the hot water pump operates normally.
3. he compressor can only be started after the ice water pump and hot water pump surely work normally.